75
Byte 6
: Event Indications 2
Bits 1-2: 24 V Supply Out of Range (High or Low)
1
Bits 3-4: Temp Sensor Failed (>140 °C or <–45 °C)
1
Bits 5-6: Power up reset
Bits 7-8: Temperature >100 °C (derated)
2
Byte 7
: Event Indications 3
Bits 1-2: Temperature >120 °C (no torque)
2
Bits 3-8: not used (sent as 1 in each bit)
Byte 8
: Not Used (sent as 0xFF)
1
Modified diagnostic value. Previous ProAct ISC and ProAct Digital Plus
versions sent Hi and Low failures separately, however they are combined
in the ProAct P-Series FL so both the High and the Low indication will be
set when either condition exists.
2
New diagnostics, added in P-Series.
Address Claimed
The Address Claimed message will be sent out shortly after power has been
applied. The Address Claimed message will also be sent out in response to a
Request for Address Claimed if the preferred address was successfully claimed.
The Request for Address Claimed can be sent to a specific Address or to the
Global Destination Address, 255. The ProAct P-Series FL will respond to a
specific query or a global query.
The Address Claimed Message will also be sent out if the ProAct P-Series FL
receives an Address Claimed message from the same Address as the receiving
node and a lower priority (higher value) NAME. The entire 8-byte value of the
NAME is used for arbitration with the Arbitrary Address Capable Field as the
Most Significant Bit.
The NAME has two user-configurable settings (Function Field and Source
Address), one factory set value (Identity Number), and the ECU instance field
corresponds to the harness code. The remaining values are all fixed. Refer to the
NAME definitions below for more details.
PGN 60928 Address Claimed (ACL)
Address Claimed / Cannot Claim Message
Transmission rate:
on start-up, on request, response to Address Claimed
Data length:
8 bytes
Data Page:
0
PDU format:
238
PDU specific:
255
Default priority:
6
Parameter Group Number:
60928 (0x00EE00)
Bytes 1-3.1: (21 bits) Identity Number, SPN 2837
Bytes 3.6-4: (11 bits) Manufacturer Code, SPN 2838
Byte 5.1: (3 bits) ECU Instance, SPN 2840
Byte 5.4: (5 bits) Function Instance, SPN 2839
Byte 6: (8 bits) Function, SPN 2841
Byte 7.1: (1 bit) Reserved
Byte 7.2: (7 bits) Vehicle System, SPN 2842
Byte 8.1: (4 bits) Vehicle System Instance, SPN 2843
Byte 8.5: (3 bits) Industry Group, SPN 2846
Byte 8.8: (1 bit) Arbitrary Address Capable, SPN 2844
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...