Manual 26659
ProAct P-Series FL Position Controller
Woodward
19
Active Closed: (default)
Active closed can be used for situations where it is safer to make the function
inactive if the wire is broken or disconnected.
Active Open:
Active open contact can be used for situations where it is safer to make the
function active if the wire is broken or disconnected.
The fuse shown in the diagram can be the same fuse that is used for the power
supply of the actuator—there is no need for an additional fuse.
Run Input
The Run Input is a configurable discrete input that causes the actuator to run
normally when active and will force the actuator current to zero (actuator goes
limp) when not active. The low power mode provides for minimal power
consumption of the device.
The Run Input can be configured as ‘Not Used’, which sets the software to
always run. With a ‘Not Used’ configuration, the Run Input wiring is not needed. If
configured for use, the Run Input must be active to run the actuator.
CAN ID Inputs
The CAN ID inputs are used to select which CAN identifiers will be used on the
CANbus. With no programming tools, the customer can select from the four pre-
programmed CAN IDs through a hard-wired code in the engine harness. This is
especially important where more than one ProAct P-Series FL is used on an
engine. If one ProAct P-Series FL actuator is replaced with another, the new
actuator will read the correct ID number from the engine harness connector upon
power-up.
Up to four ProAct P-Series FL actuators with the same configuration can be on the
same CANbus, however, each must have a different device address. The CAN
device source address is determined by using the CAN ID HI and LO discrete inputs
upon power-up of the actuator (see Table 2-1). The TRUE/FALSE state is based on
the actuator’s configuration settings (see Table 2-2).
ProAct P-Series
FL ID Number
1
2
3
4
CAN ID HI
FALSE state
FALSE state
TRUE state
TRUE state
CAN ID LO
FALSE state
TRUE state
FALSE state
TRUE state
Table 2-1. ProAct P-Series FL CAN ID Number
ProAct P-Series
FL Configuration
High Side
Switch,
Active Closed
High Side
Switch,
Active Open
Low Side
Switch,
Active Closed
Low Side
Switch,
Active Open
TRUE state
Closed /
High (+V)
Open/
Low (Gnd)
Closed/
Low (Gnd)
Open/
High (+V)
FALSE state
Open/
Low (Gnd)
Closed/
High (+V)
Open/
High (+V)
Closed/
Low (Gnd)
Table 2-2. Discrete In Configuration Logic
The CAN address high and low discrete inputs must be wired prior to
power-up to be registered.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...