ProAct P-Series FL Position Controller
Manual 26659
54
Woodward
Analog Out Tab
The analog output range is selected by jumper 1. The Analog Out tab provides
the analog output configuration settings for both output ranges.
Figure 5-5. Configuration Editor—Analog Out Tab
Analog Output Section
An output selection and scaling of position to milliamps is provided in this section.
Analog Output Selection
The analog output is scaled from the position percent to a 0-20 mA current or 0-5
V (dc) voltage output signal. The range is automatically selected by the JPR1
position, determined at power-up. The output functionality can be configured as
follows:
None
—The analog output is turned off.
Actual Position
—Selects an actual position analog output signal.
Position Setpoint
—Selects a position setpoint analog output signal.
Default: Actual Position
4..20 mA Output Section
Position Minimum
Specifies the value of the selected position (actual or setpoint) at the output
current minimum setting. Setting the position minimum higher than the position
maximum is allowed to provide for a reverse acting signal as needed.
Allowed values: 0-100 % Default: 0 %
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...