ProAct P-Series FL Position Controller
Manual 26659
52
Woodward
Output Minimum
The position command value corresponding to the input minimum setting.
Allowed values: 0-100 %. Default: 0 %
Output Maximum
The position command value corresponding to the input maximum setting.
Allowed values: 0-100 %. Default: 100 %
Diagnostic Minimum
Specifies the minimum normal value for the analog input. When configured, an
Analog Input Low alarm or shutdown fault is triggered when the input falls below
this setting.
Allowed values: 0-25 mA. Default: 2 mA
Diagnostic Maximum
Specifies the maximum normal value for the analog input. When configured, an
Analog Input High alarm or shutdown fault is triggered when the input increases
above this setting.
Allowed values: 0-25 mA. Default: 22 mA
0..200 mA Input Section
This section provides the analog input scaling and diagnostic settings, used
when the 0-200 mA range is selected.
Current Minimum
The value of the input at the output minimum setting. Setting the minimum higher
than the maximum is allowed to provide for a reverse acting signal as needed.
Allowed values: 0-200 mA. Default: 20 mA
Current Maximum
The value of the input at the output maximum setting, used for the analog input
current to position command scaling.
Allowed values: 0-200 mA. Default: 180 mA
Output Minimum
The position command value corresponding to the input minimum setting.
Allowed values: 0-100 %. Default: 0 %
Output Maximum
The position command value corresponding to the input maximum setting.
Allowed values: 0-100 %. Default: 100 %
Diagnostic Minimum
Specifies the minimum normal value for the analog input. When configured, an
Analog Input Low alarm or shutdown fault is triggered when the input falls below
this setting.
Allowed values: 0-200 mA. Default: 10 mA
Diagnostic Maximum
Specifies the maximum normal value for the analog input. When configured, an
Analog Input High alarm or shutdown fault is triggered when the input increases
above this setting.
Allowed values: 0-200 mA. Default: 190 mA
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...