Wires must be terminated with ferrules for use in the terminal blocks. For 16
AWG (1.3 mm²) wires, use ferrule P/N 1606-667; for 18 AWG (0.8 mm²) wires,
use ferrule P/N 1602-1157; and for 20 AWG (0.5 mm²) wires, use ferrule P/N
1602-997.
Remove approximately 100 mm (4 inches) of the overall cable jacket to provide a
sufficient service loop inside the Actuator to land the individual signal wires on
the proper internal terminal. Strip approximately 10 mm (0.4 inch) of insulation
from each individual wire and crimp on a wire ferrule to the end of each wire. Use
the proper crimp tool, “CRIMPFOX 6H” Woodward part number 8996-2197 to
crimp the ferrules onto the signal wires with a hexagonal crimp. The wire should
extend to the end of the ferrule, but not beyond it. If the wire extends beyond the
end of the ferrule, cut the excess wire off with wire cutters. The ferrule assures
the signal wire does not slip out of the terminal block in high vibration
environments. Tinning (soldering) the ends is not an acceptable option since the
spring terminals will not grip the wires as well.
The jumper used for the ProAct P-Series FL is Woodward P/N 1606-848.
Woodward hardware part numbers for access cover hardware:
6-32 screw:
1069-923
#6 washer (w/seal):
1386-125
10-32 screw:
188292
#10 washer:
186044
Due to the hazardous location listings associated with this product,
proper wire type and wiring practices are critical to operation.
Do not connect any cable grounds to “instrument ground”, “control
ground”, or any non-earth ground system. Make all required
electrical connections based on the wiring diagram (Figure 2-2).
Description of Electrical I/O
This section provides a schematic representation of each input/output. Additional
information can be found in the I/O specifications of the Appendix.
Supply Power
10
9
Fuse
Power Supply
ProAct
Input Power
Reverse
Voltage
Protection .
Internal
Power
Supply.
TB 10 = Supply Power Plus
TB 9 = Supply Power Minus
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...