ProAct P-Series FL Position Controller
Manual 26659
48
Woodward
CAN Tab
Figure 5-2. Configuration Editor—CAN Tab
General Settings Section
CAN Data Rate
Selects the desired CAN data rate.
Options are: 125, 250, 500, or 1000 kbits/s
Default: 250 kbps
CAN ID Low Input
Select the desired discrete input for the CAN ID Low function, used in
conjunction with the CAN ID High input to determine the harness code on
power-up.
Options: Input 1, Input 2, Input 3
Default: Input 2
CAN ID High Input
Select the desired discrete input for the CAN ID High function, used in
conjunction with the CAN ID Low input to determine the harness code on
power-up.
Options: Input 1, Input 2, Input 3
Default: Input 3