ProAct P-Series FL Position Controller
Manual 26659
82
Woodward
Error Flag
Description
Possible Source
Possible Action
Analog Input Fault This error flag will be set if
the analog input is higher
or lower than the
configured limits.
Analog input is driven outside of the
diagnostic limit.
Diagnostic limit is setup incorrectly.
Input configuration (4 to 20) mA vs
(0 to 5) V mismatch.
Input is incorrectly wired - open or
short or connected to the wrong
input (4 to 20) mA vs (0 to 5) V.
Check signal and fix incorrect
signal level. Verify reading of
input on the Service Tool.
Verify correct diagnostic limits.
Verify input configuration.
Correct wiring problem.
PWM Input Fault
This error flag will be set if
the PWM input duty cycle
is higher or lower than the
configured limits.
PWM input is driven outside of the
diagnostic limit. PWM voltage levels
out of specification range.
Diagnostic limit is setup incorrectly.
Input is incorrectly wired.
Check signal and fix incorrect
signal level. Verify reading of
input on the Service Tool.
Verify correct diagnostic limits.
Correct wiring problem.
Supply Voltage
Fault
The power supply voltage
is higher than the
diagnostic limits.
The Power supply voltage
is lower than the
diagnostic limits.
Bad or damaged battery.
Defective battery charging system.
Incorrect setting of power supply
voltage level.
Power supply wiring too long or too
thin. Actuator will flag low voltage
during higher power uses.
The actuator’s input is damaged.
Replace battery.
Fix battery charging system.
Set correct voltage levels on
power supply.
Make sure wiring is of the
correct thickness and length
according to manual.
Verify input power reading using
the Service Tool. If bad, return
unit to Woodward for repair.
Electrical
Temperature
>100 °C or
>120 °C
High internal temperature.
The temperature inside
the actuator is higher than
the programmed limits.
Actuator has been placed in an
environment that is too hot.
The internal temperature sensor is
defective.
Check ambient temperature
around the actuator.
Lower temperature by adding
cooling, heat shielding, moving
the unit, etc.
Verify internal electrical
temperature reading using the
Service Tool.
If the temperatures seem
normal, could indicate a problem
with the temperature sensor.
Electrical
Temperature
Fault
This error is set if the
temperature inside the
actuator is outside the
limits allowed by the
specifications.
The actuator has been placed in an
environment that is too hot or too
cold.
The internal temperature sensor is
defective.
Lower the actuator temperature
by adding cooling, heat
shielding, moving the unit, etc.
Increase temperature by adding
heat.
Verify internal electrical
temperature reading using the
Service Tool.
Return unit to Woodward for
repair.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...