ProAct P-Series FL Position Controller
Manual 26659
34
Woodward
Failure levels (0 to 5) V (dc) mode: >4.8 V (dc) and < 0.2 V (dc), set by customer
variable
Failure levels (4 to 20) mA mode: >22 mA and <2 mA, set by customer variable
Failure levels (0 to 200) mA mode: >190 mA and <5 mA, set by customer
variable
Persistence: 100 ms when not configured for redundant demands
Persistence: 10 ms when configured for redundant demands
Configuration options: Off, Alarm, Shutdown
CAN Demand Fault
This is an indication that CAN messages are not valid, not received, or received
at a rate slower than the configured minimum update rate (CAN Fail Timeout). A
CAN signal in the “Error” or “Not Supported” range is considered not valid
(0xFAFF-0xFFFF). This diagnostic fault only applies to commands configured to
be received over CAN (i.e. CAN Demand configured).
Configuration options: Off, Alarm, Shutdown
CAN Communications Fault
Unable to communicate with the CAN bus. Could indicate a bus problem or an
address contention.
Configuration options: Off, Alarm, Shutdown
CAN Stop Command
Indicates a STOP command was received over the CAN Command message.
CAN demand must be configured for this feature to be enabled. Not available in
Legacy mode.
Configuration options: none - dedicated Shutdown
This is a hard-coded shutdown. The actuator will go limp if this condition is
detected.
Run Enable Shutdown
Indicates the Run Enable discrete input is opened. The shutdown is only active
when Run Enable is configured for use.
Configuration options: Not Used or Shutdown
When configured for use, this is a hard-coded shutdown. The actuator will go
limp if this condition is detected.
Demand Tracking Fault
Indicates the backup position command does not match the primary position
command.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...