ProAct P-Series FL Position Controller
Manual 26659
26
Woodward
Actuator Features Description
As you review the following features, keep in mind that most applications only
require a few of the functions to be activated. The choices are made available to
provide maximum flexibility in a single package. The user must set up the
actuator direction, min and max position calibration, position command input, and
desired I/O. The user can choose all or none of the CAN settings,
alarm/shutdown functions and logic functions depending on the application.
The actuator I/O consists of input power, a PWM input, one analog input,
3 discrete inputs, one analog output, one status discrete output and a CAN
communication port. The analog input can be either (4 to 20) mA, (0 to 5) V (dc),
or (0 to 200) mA. The analog output can be either (4 to 20) mA or (0 to 5) V (dc).
The actuator maintains the position commanded by the supervisory control, as
determined by the input redundancy manager. Internal position feedback is used
to assure positive positioning. The actuator output shaft rotation is software
configured for either a clockwise (CW) or counter-clockwise (CCW) output shaft
rotation. An actuator correction curve is provided to configure a demanded
position versus actual position for non-linear systems.
Customer
Controller
P-Series
Run Enable
Status
Power Input
(18-32Vdc)
Service Tool
RS-232
Actual Position (4-20mA)
Position Demand
(Analog/PWM/CAN)
Figure 3-1. Typical System Overview
Driver Input Power
The ProAct P-Series FL will handle a voltage range of (18 to 32) V (dc) at full
specified torque. The actuator is functional in the range of (8 to 40) V (dc), but
accuracy and/or torque can be diminished at the extreme ends of this range.
The supply voltage diagnostic trip levels are below 17 V (dc) and above 33 V (dc)
with a timeout to avoid nuisance alarms. The unit can be configured to either
alarm or shutdown upon detection of a supply voltage fault.
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...