Failure levels: Set by customer variable, |Error| > Tracking Error Max
Persistence: Set by customer variable, Tracking Error Delay
Configuration options: Off, Alarm, Shutdown
If configured as an alarm, the actuator will attempt to continue normal operation
using the trusted input. The trusted input is configurable and is based on the
‘Switch control to Backup demand on track error’ selection.
Internal Fault
Indicates that an internal failure has occurred. The Internal Shutdowns page of
the Service Tool indicates the exact cause.
Configuration options: none - dedicated Shutdown
If detected, the actuator will use current control to execute the shutdown action
(min, max, limp).