Alarm / Shutdown Fault Settings
Fault Selection (Shutdown or Alarm)
Set the desired action for each of the faults from the list. Enable the faults that
are to be detected. Setting the selection to a Shutdown positions the output to
the Shutdown Direction setting when a fault occurs. Setting the selection to an
Alarm allows the unit to attempt continued running but provides an indication that
the condition was detected (logged fault).
Default: unchecked (disabled)
Fault Description
See Chapter 3 for detailed descriptions for the following fault conditions.
Supply Voltage Fault
Position
Error
Temperature Sensor Failed (internal electronics)
Temp > 100 °C (derated)
Temp > 120 °C
Loss of All Position Demands
Demand Tracking Fault
CAN Communication Fault
Analog Demand Failed
PWM Demand Failed
CAN Demand Failed
The following are dedicated shutdown conditions.
Internal
Shutdown
Run Enable Shutdown (Run/Stop)
CAN Stop Command
It is recommended that all faults be configured as shutdowns and
that ‘Enable Fault Latching’ be selected. This ensures maximum fault
protection and prevents erratic on/off fault behavior.
Enable Fault Latching
Set to either latching (checked) or non-latching. When set to latching, a reset
command or a power cycle must be issued to clear the fault. When non-latching
is configured, normal actuator operation is restored once the fault condition
ceases to exist. The fault log continues to indicate any faults that have occurred,
but are no longer active, until the logged alarms and shutdowns are reset.
Default: checked
Shutdown Direction (firmware 5418-6133)
Specifies the action when a shutdown condition is detected and active.
Options are: Go to Min (0 %), Go to Max (100 %), or Go Limp (no drive current).
Default: Go To Min (0 %)
Shutdown Action (firmware 5418-6507 and newer)
Specifies the action when a shutdown condition is detected and active.
Options are: Go to Min (0 %), Go to Max (100 %), Go Limp (no drive current),
Min then Limp, or Max then Limp.
Default: Go To Min (0 %)
Содержание ProAct P Series FL
Страница 10: ...ProAct P Series FL Position Controller Manual 26659 viii Woodward ...
Страница 15: ...Manual 26659 ProAct P Series FL Position Controller Woodward 5 Figure 1 1 ProAct P Series FL Outline Drawing ...
Страница 23: ...Manual 26659 ProAct P Series FL Position Controller Woodward 13 Figure 2 2a Actuator Wiring Diagram ...
Страница 24: ...ProAct P Series FL Position Controller Manual 26659 14 Woodward Figure 2 2b Actuator Wiring Diagram Notes ...
Страница 79: ...Manual 26659 ProAct P Series FL Position Controller Woodward 69 Figure 6 8 Strip Chart Properties Window ...
Страница 108: ...ProAct P Series FL Position Controller Manual 26659 98 Woodward Declarations ...
Страница 109: ...Manual 26659 ProAct P Series FL Position Controller Woodward 99 ...