E6581697
F-11
6
■
Setting of switching terminals
To switch to motor 2, assign the following functions to a terminal not being used. It is also possible to switch
to acceleration/deceleration 2 (AD2). Refer to section 6.15.1 for details.
It is possible to set 3 functions for terminal F and R, and 2 functions for terminal S1 and S2.
Input terminal function number
24
AD2
26
AD3
28
VF2
32
OCS2
Parameters changed from applicable parameters and
default standards
OFF OFF OFF OFF
Default setting :
pt
,
vl
,
vlv
,
vb
,
thr
,
acc
,
dec
,
fs02
,
f601
ON OFF OFF OFF
acc
¤
fs00
、
dec
¤
f501
、
f502
¤
fs03
OFF ON OFF OFF
acc
¤
fs10
、
dec
¤
f511
、
f502
¤
fs12
During stop :
pt
¤
V/F constant ,
vl
¤
f170
,
vlv
¤
f171
,
vb
¤
f172
,
thr
¤
f173
OFF OFF ON OFF
During run :
vl
¤
f170
,
vlv
¤
f171
,
vb
¤
f172
,
thr
¤
f173
OFF OFF OFF ON
f601
¤
f185
Note 1: Each of the following numbers (25, 27, 29, 33) are reverse signals.
Note 2: Switching
pt
and "V/F constant" cannot be done while running. Stop the motor before changing.
vl
and
f170
,
vlv
and
f171
,
vb
and
f172
,
thr
and
f173
can be switched while
running.
Note 3: Integral value of motor electronic thermal is kept, after the motor switching.
However, the setting that can memorize an integral value is possible.
■
Example of setting a terminal for switching : Sink logic
F (F: Forward run)
CC
S2(VF2)
R(OCS2)
S1(AD2)
Forward run command
2nd acceleration/deceleration switch
2nd stall prevention operation switch
2nd V/F setting switch
Содержание TOSVERT VF-MB1