background image

 

Solid State Relays (Single-phase)

 G3PB

1

Solid State Relays (Single-phase)

G3PB

Compact, Slim-profile SSR with Heat Sink, 
Offering Heater Control for 480-VAC Rated 
Loads

• Compact design achieved by optimizing heat sink shape.

• DIN track mounting possible in addition to screw mounting.

• Conforms to CE Marking, EN (VDE approval), CSA, and VDE 

standards. 
(UL pending)

Note:

Refer to 

Precautions

 on page 5.

Model Number Structure

Model Number Legend

1. Basic Model Name

G3PB:

Solid State Relay

2. Rated Load Power Supply Voltage

5:

480 VAC

3. Rated Load Current

15:

15 A

25:

25 A

35:

35 A

45:

45 A

4. Terminal Type

B:

Screw terminals

5. Number of Elements

Blank:

Single-phase models

6. Construction

Blank:

DIN track mounting and built-in heat sink

7. Certification

VD:

Certified by CSA and VDE

Ordering Information

List of Models

Note:

The applicable load current varies depending on the ambient temperature. For details, refer to 

Load Current vs. Ambient Temperature

 in 

Engineering Data.

Accessories (Order Separately)

1

2 3 4

5 6

7

G3PB-

@@@-@@-@

Isolation method

Zero cross 

function

Operation 

indicator

Rated input 

voltage

Rated output load

(See note.)

Model number

Phototriac coupler

Yes

Yes (yellow)

12 to 24 VDC

15 A, 200 to 480 VAC

G3PB-515B-VD 12 to 24 VDC

25 A, 200 to 480 VAC

G3PB-525B-VD 12 to 24 VDC

35 A, 200 to 480 VAC

G3PB-535B-VD 12 to 24 VDC

45 A, 200 to 480 VAC

G3PB-545B-VD 12 to 24 VDC

Mounting Track

50 cm (1) x 7.3 mm (t)

PFP-50N

1 m (1) x 7.3 mm (t)

PFP-100N

1 m (1) x 16 mm (t)

PFP-100N2

Содержание G3PB

Страница 1: ...ents Blank Single phase models 6 Construction Blank DIN track mounting and built in heat sink 7 Certification VD Certified by CSA and VDE Ordering Information List of Models Note The applicable load current varies depending on the ambient temperature For details refer to Load Current vs Ambient Temperature in Engineering Data Accessories Order Separately 1 2 3 4 5 6 7 G3PB Isolation method Zero cr...

Страница 2: ...00 VAC Item G3PB 515B VD G3PB 525B VD G3PB 535B VD G3PB 545B VD Operate time 1 2 of load power source cycle 1 ms max Release time 1 2 of load power source cycle 1 ms max Output ON voltage drop 1 8 V RMS max Leakage current 20 mA max at 480 VAC Insulation resistance 100 MΩ min at 500 VDC Dielectric strength 2 500 VAC 50 60 Hz for 1 min Vibration resistance Destruction 10 to 55 to 10 Hz 0 375 mm sin...

Страница 3: ... impedance kΩ Input current mA 30 25 20 15 10 7 0 30 20 0 20 40 60 80 100 G3PB 525B VD G3PB 515B VD Load current A Ambient temperature C 50 45 40 35 30 20 10 0 30 20 0 20 40 60 80 100 14 18 25 G3PB 545B VD G3PB 535B VD Ambient temperature C Load current A 250 200 150 100 50 0 Inrush current A Peak 10 30 50 100 300 500 1 000 3 000 5 000 Energized time ms Inrush current A Peak Energized time ms 250 ...

Страница 4: ...0 85 100 1 2 A1 A2 Trigger circuit Input circuit G3PB 535B VD G3PB 545B VD Mounting Holes Terminal Arrangement Internal Circuit Diagram Output side Input side Note Without terminal cover Note With terminal cover 25 0 3 90 0 3 Two 4 5 dia or M4 68 24 13 4 6 1 Two M3 5 Two M5 25 0 2 44 5 max 100 max 90 0 2 80 4 6 dia Elliptical hole 4 6 x 5 6 90 85 100 1 2 A1 A2 Input circuit Trigger circuit PFP 100...

Страница 5: ...uch as aluminum or steel If a material with high thermal resistance such as wood is used heat generated by the G3PB may cause fire or burning 3 Perform wiring and tighten screws correctly according to the fol lowing precautions If wiring is incorrect or screws are not tight ened sufficiently the G3PB may be damaged by abnormal heat generated when the power is turned ON Make sure that all lead wire...

Страница 6: ...oper ventilation of the control panel A heat exchanger if used should be located in front of the SSR Units to ensure the efficiency of the heat exchanger Do not use or store in locations subject to direct sunlight Do not use in locations subject to ambient temperatures outside the range 30 to 80 C Do not use in locations subject to relative humidity outside the range 45 to 85 or locations subject ...

Страница 7: ... heat build up For this reason under conditions where heat dissipation is not good due to poor ventilation and where heat may build up easily the actual temperature of the G3PB may exceed the rated value resulting in malfunction or burning When using the G3PB design the system to allow heat dissipation sufficient to stay below the Load Current vs Ambient Temperature characteristic curve Note also ...

Страница 8: ...exceed the individual price of the product on which liability is asserted IN NO EVENT SHALL OMRON BE RESPONSIBLE FOR WARRANTY REPAIR OR OTHER CLAIMS REGARDING THE PRODUCTS UNLESS OMRON S ANALYSIS CONFIRMS THAT THE PRODUCTS WERE PROPERLY HANDLED STORED INSTALLED AND MAINTAINED AND NOT SUBJECT TO CONTAMINATION ABUSE MISUSE OR INAPPROPRIATE MODIFICATION OR REPAIR Application Considerations SUITABILIT...

Отзывы: