Solid State Relays (Single-phase)
G3PB
Specifications
■
Ratings (at an Ambient Temperature of 25
°
C)
Input
Output
Note:
The applicable load current varies depending on the ambient temperature. For details, refer to
Load Current vs. Ambient Temperature
in
Engineering Data.
■
Characteristics
Item
Common
Rated voltage
12 to 24 VDC
Operating voltage range
9.6 to 30 VDC
Rated input current
7 mA max.
Must operate voltage
9.6 VDC max.
Must release voltage
1 VDC min.
Item
G3PB-515B-VD
G3PB-525B-VD
G3PB-535B-VD
G3PB-545B-VD
Rated load voltage
200 to 480 VAC (50/60 Hz)
Load voltage range
180 to 528 VAC (50/60 Hz)
Applicable load current (See note.)
0.1 to 15 A (at 40
°
C)
0.1 to 25 A (at 40
°
C)
0.5 to 35 A (at 25
°
C)
0.5 to 45 A (at 25
°
C)
Inrush current resistance (peak value)
150 A
(60 Hz, 1 cycle)
220 A
(60 Hz, 1 cycle)
440 A
(60 Hz, 1 cycle)
Permissible I
2
t
(half 60-Hz wave)
128 A
2
s
1,350 A
2
s
6,600 A
2
s
Applicable load
(with Class-1 AC resistive load)
6 kW max.
(at 400 VAC)
10 kW max.
(at 400 VAC)
14 kW max.
(at 400 VAC)
18 kW max.
(at 400 VAC)
Item
G3PB-515B-VD
G3PB-525B-VD
G3PB-535B-VD
G3PB-545B-VD
Operate time
1/2 of load power source cycle + 1 ms max.
Release time
1/2 of load power source cycle + 1 ms max.
Output ON voltage drop
1.8 V (RMS) max.
Leakage current
20 mA max. (at 480 VAC)
Insulation resistance
100 M
Ω
min. (at 500 VDC)
Dielectric strength
2,500 VAC, 50/60 Hz for 1 min
Vibration resistance
Destruction: 10 to 55 to 10 Hz, 0.375-mm single amplitude (0.75-mm double amplitude)
(Mounted to DIN track)
Shock resistance
Destruction: 294 m/s
2
(DIN track mounting)
Ambient temperature
Operating:–30
°
C to 80
°
C (with no icing or condensation)
Storage: –30
°
C to 100
°
C (with no icing or condensation)
Ambient humidity
Operating: 45% to 85%
Certified standards
CSA22.2 No. 14
EN60947-4-3
EMC
Emission
EN55011 Group 1 Class B
Immunity
ESD
IEC947-4-3, EN61000-4-2
4 kV contact discharge
8 kV air discharge
Immunity
Electromagnetic
IEC947-4-3, EN61000-4-3
10 V/m (80 MHz to 1 GHz)
Immunity
EFT
IEC947-4-3, EN61000-4-4
2 kV AC power-signal line
Immunity
Surge transient
IEC947-4-3, EN61000-4-5
Normal mode
±
1 kV, Common mode
±
2 kV
Immunity
RF disturbance
IEC947-4-3, EN61000-4-6
10 V (0.15 to 80 MHz)
Immunity
Dips
IEC947-4-3, EN61000-4-11
Weight
Approx. 240 g
Approx. 400 g