Error code
Problem
Possible causes
Remedies
Output frequency
upper limit
An attempt was made to operate at a
frequency higher than 10 times the base
frequency (
or
).
Operate at a frequency within 10 times the
base frequency.
Operation panel key
alarm
The RUN or STOP key is held down for
more than 20 seconds.
The RUN or STOP key is faulty.
Check the operation panel.
S3 terminal alarm
Slide switch SW2 and parameter
f147
settings are different.
Match the settings of SW2 and
f147
.
Power supply OFF and ON after these
settings.
Auto-tuning
Auto-tuning in process
Normal if it the message disappears after a
few seconds.
Break in analog
signal cable
The signal input via VIC is below the
analog signal detection level set with
and setting value of
is
one or more.
Check the cables for breaks. And check the
setting of input signal or setting value of
and
.
In forced operation
“
” and operation frequency is
displayed alternately in operation of forced
fire-speed control.
It is normal the alarm is gone out after the
forced fire-speed control operation.
STO signal OFF
STO terminal is in open-circuit.
Close STO and + SU circuit.
/
Password verification
result
After the password setting (
f738
), the
password was input to
f739
(password
verification).
If the password is correct,
pass
is displayed
and if it is incorrect,
fail
is displayed.
/
Switching display of
Easy setting mode /
Standard setting
mode
The EASY key was pushed in the
standard monitor mode.
When
easy
is displayed, setting mode
becomes easy setting mode. When
std
is
displayed, it becomes standard setting mode.
Note 2)
Input requirement of
region setting
A region setting is not input yet.
Power supplied to the inverter at first time
As checking the region setting parameter
set
is set to
0
, inverter return to default
setting.
As
typ
is set to
13
, inverter return to
default setting.
Set a region setting by using setting dial.
Refer to section 3.1.
No trip of past trip
No new record of past trip, after past trips
were clear.
Normal operation.
No detailed
information of past
trip
The detailed information of past trip is
read by pushing the center of setting dial
during blinking
nerr
⇔
number.
Normal operation.
To be returned by pressing MODE key.
[Prealarm display]
Overcurrent alarm
Same as
(overcurrent)
Overvoltage alarm
Same as
(overvoltage)
Overload alarm
Same as
and
(overload)
Overheat alarm
Same as
(overheat)
Communication alarm
Same as
err5
(communication fault)
If two or more problems arise simultaneously, one of the following alarms appears and blinks.
,
,
The blinking alarms
,
,
,
h
,
t
are displayed in this order from left to right.
Note 2)
is blinking after power supply is on. In this time, the keys are not operated.
But parameter
set
is lighting as same as other parameters and is not blinking.