E6581697
F-58
6
6.20 PID
control
fpid
:
Process input value of PID
f369
: PID control feedback signal
control
selection
f359
: PID control waiting time
f372
: Process increasing rate
f360
: PID control
(speed type PID control)
f361
:
Delay filter
f373
:
Process decreasing rate
f362
: Proportional gain
f380
: PID forward/reverse
f363
: Integral gain
characteristics selection
f366
: Differential gain
f389
: PID control reference signal
f367
:
Process upper limit
selection
f368
: Process lower limit
Function
Using feedback signals (4 to 20mA, 0 to 10V) from a detector, process control can be exercised, for
example, to keep the airflow, amount of flow or pressure constant.
Or, it is also possible to always set 0 for integral and differential at terminal input.
[Parameter setting]
Title
Function
Adjustment range
Default setting
fpid
Process input value of PID control
f368
-
(Hz)
0.0
f359
PID control waiting time
0-2400 (s)
0
f360
PID
control
0: Disabled
1: Process type PID control
2: Speed type PID control
0
f361
Delay filter
0.0-25.0 (s)
0.1
f362
Proportional gain
0.01-100.0
0.30
f363
Integral gain
0.01-100.0
0.20
f366
Differential gain
0.00-2.55
0.00
f367
Process upper limit
0.0-
fh
(Hz)
*1
f368
Process lower limit
0.0-
(Hz)
0.0
f369
PID control feedback signal selection
0: Disabled, 1: VIA, 2: VIB, 3: VIC
4 to 6: -
0
f372
Process increasing rate (speed type
PID control)
0.1-600.0 (s)
10.0
f373
Process decreasing rate
0.1-600.0 (s)
10.0