E6581697
F-35
6
,
In case of parameter
aul
=
2
(Variable torque characteristic (120%-60s)) setting
PWM carrier frequency
(Parameter
f300
)
VFMB1-
Ambient
temperature
2.0kHz 2.1k
-
4.0 kHz 4.1k
-
12.0 kHz 12.1k
-
16.0 kHz
4004PL
40
C or less
2.1 A
1.5 A
1.5 A
1.2 A
4007PL
40
C or less
3.0 A
2.3 A
2.3 A
1.8 A
4015PL
40
C or less
5.4 A
4.1 A
4.1 A
3.3 A
4022PL
40
C or less
6.9 A
5.5 A
5.5 A
4.4 A
4037PL
40
C or less
11.9 A
9.5 A
9.5 A
7.6 A
40
C or less
17.0 A
13.0 A
11.5 A
40
50
C
15.3 A
13.0 A
11.5 A
4055PL
50
60
C
13.6 A
11.4 A
9.2 A
40
C or less
23.0 A
17.0 A
14.0 A
40
50
C
20.7 A
17.0 A
14.0 A
4075PL
50
60
C
18.4 A
13.6 A
10.9 A
40
C or less
33.0 A
25.0 A
20.0 A
40
50
C
29.7 A
25.0 A
20.0 A
4110PL
50
60
C
26.4 A
19.4 A
15.2 A
40
C or less
40.0 A
30.0 A
26.0 A
40
50
C
36.0 A
30.0 A
26.0 A
4150PL
50
60
C
36.0 A
23.0 A
18.0 A
* If ambient temperature exceeds 40°C (or 50°C), reduce current according to table above.
* In case of
=
2
setting, be sure to install the input AC reactor (ACL) between power supply and inverter
and use at ambient temperature 40°C or less.
* Regarding current reduction in detail, refer to added instruction manual “Explanation of load reduction”.
* If
parameter
f316
=
0
or
2
and current is increased to the automatic reduction level, the
ol
alarm occurs.
If current is increased further,
ol3
trips.
In this case, to avoid such trips, reduce the stall prevention level (
f601
) properly.
* If
parameter
f316
(Carrier frequency control mode selection) =
2
or
3
, set parameter
f300
(PWM
carrier frequency) below 4.0kHz. Output voltage may reduce.
* PWM carrier frequency is increased at high output frequency area to be stable the operation, even if
f300
is set to low PWM carrier frequency.