E6581697
C-8
3
(2) Setting of frequency using external signals to terminal block (
=
,
or
)
Frequency setting
1)
Setting the frequency using external potentiometer
2)
Setting the frequency using voltage input (0-10V)
3)
Setting the frequency using current input (4-20mA)
4)
Setting the frequency using voltage input (-10-+10V)
: Setting frequency
using potentiometer
★
Potentiometer
Setting frequency using the potentiometer (1k -10k
, 1/4W)
Refer to section 6.5.2 for detailed adjustment.
Frequency
50 or 60Hz
0
MIN
MAX
PP
CC
V I A
Note) Set parameter
=
,
, or
.
★
Voltage signal
Setting frequency using voltage signals (0
-
10V).
Refer to section 6.5.2 for detailed adjustment.
Frequency
50 or 60Hz
0
0Vdc
10Vdc
Note) Set parameter
=
,
=
.
CC
V I B
+
-
: Voltage signal 0-10Vdc
★
Current Signal
Current signal Setting frequency using current signals (4
-
20mA).
Refer to section 6.5.2 for detailed adjustment.
Frequency
50 or 60Hz
0
4mAdc 20mAdc
* Setting of parameters also allow 0-20mAdc.
Note) Set parameter
=
.
CC
V I C
+
-
: Current signal 4-20mAdc
Note) Set parameter
f107
=
1
,
=
.
CC
V IB
+
-
: Voltage signal -10-+10Vdc
★
Voltage signal
Set the frequency using voltage signals (-10-+10V).
Refer to section 6.5.2 for detailed adjustment.
-10Vdc
+10Vdc
Forward run
Reverse run
50 or 60Hz
50 or 60Hz