E6581697
C-4
3
3.2
Simplified Operation of the VF-MB1
The procedures for setting operation frequency and the methods of operation can be selected from the following.
Run / Stop
:
(1) Run and stop using the panel keypad
(2) Run and stop using external signals to terminal
board
Setting the frequency
: (1) Setting using setting dial
(2) Setting using external signals to terminal board
(0-10Vdc,
4-20mAdc)
Use the basic parameters
(command mode selection)
and (frequency setting mode selection) for selection.
[Parameter setting]
Title
Function
Adjustment range
Default setting
Command mode selection
0: Terminal board
1: Panel keypad (including extension
panel)
2: RS485 communication
3: CANopen communication
4: Communication option
1
Frequency setting mode
selection
0: Setting dial 1(save even if power is off)
1: Terminal board VIA
2: Terminal board VIB
3: Setting dial 2(press in center to save)
4: RS485 communication
5: UP/DOWN from external logic input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
0
☆
fmod
=
0
(setting dial 1) is the mode that after the frequency is set by the setting dial, the frequency is saved
even if the power is turned off.
☆
Refer to section 5.6 for details about
=
to
and
11
.