Branch circuit protection must be provided in accordance with the Canadian Electrical Code and any additional
local codes.
9.2.3
Compliance with Peripheral devices
Use the UL listed fuses at connecting to power supply.
Short circuit test is performed under the condition of the power supply short-circuit currents in below.
These interrupting capacities and fuse rating currents depend on the applicable motor capacities.
AIC, Fuse and Wire sizes
Inverter model
Voltage
(V)
Input
withstand
rating (kA)
Output
Interrupt
rating (kA)
Branch circuit
protection
Rating
(A)
Cable sizes of
power circuit
Earth Cable
Markig
Y
(1)
X
(2)
Z1
Z2
-
-
VFMB1S-2002PL
240
1
5
Class CC
7
AWG 14
AWG 14
VFMB1S-2004PL
240
1
5
Class J
15
AWG 14
AWG 14
VFMB1S-2007PL
240
1
5
Class J
25
AWG 14
AWG 14
VFMB1S-2015PL
240
1
5
Class J
40
AWG 10
AWG 12
VFMB1S-2022PL
240
1
5
Class J
45
AWG 10
AWG 10
VFMB1-4004PL
500
5
5
Class CC
6
AWG 14
AWG 14
VFMB1-4007PL
500
5
5
Class CC
6
AWG 14
AWG 14
VFMB1-4015PL
500
5
5
Class CC
12
AWG 14
AWG 14
VFMB1-4022PL
500
5
5
Class J
15
AWG 14
AWG 14
VFMB1-4037PL
500
5
5
Class J
25
AWG 12
AWG 14
VFMB1-4055PL
500
22
22
Class J
40
AWG 10
AWG 10
VFMB1-4075PL
500
22
22
Class J
40
AWG 8
AWG 10
VFMB1-4110PL
500
22
22
Class J
60
AWG 8
AWG 10
VFMB1-4150PL
500
22
22
Class J
70
AWG 6
AWG 10
Suitable for use on a circuit capable of delivering not more than___X___rms symmetrical kilo Amperes,___Y___Volts
maximum, when protected by___Z1___with a maximum rating of___Z2___.
(1) Input withstand rating is that for which the product has been designed thermally. Installation on a supply greater than
this level will require additional inductance to satisfy this level.
(2) Output interrupt rating relies on Integral solid state short circuit protection. This does not provide branch circuit
protection. Branch circuit protection must be provided in accordance with the National Electrical Code and any
additional local codes. This is dependant on the type of installation.
9.2.4
Motor thermal protection
Selects the electronic thermal protection characteristics that fit with the ratings and characteristics of the motor.
(Refer to section 3.5)
In case of multi motor operation with one inverter, thermal relay should be connected to each motor.