E6581697
K-12
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0334 Light-load
high-
speed operation
heavy load
detection time
s 0.1/0.1
0.0-10.0
0.5 6.17
0335 Switching
load
torque during
power running
% 1/0.01
-250-
+250
50
0336 Heavy-load
torque
during power
running
% 1/0.01
-250-
+250
100
0337 Heavy-load
torque
during constant
power running
% 1/0.01
-250-
+250
50
0338
Switching load
torque during
regenerative
braking
% 1/0.01
-250-
+250
50
0340
Creeping time 1
s
0.01/0.01
0.00-10.00
0.00
6.18.1
0341 Braking
mode
selection
- -
0: Disabled
1: Forward winding up
2: Reverse winding up
3: Horizontal operation
0
0342 Load
portion
torque input
selection
- -
0: Disabled
1: VIA
2: VIB
3: VIC
4:
f343
0
0343
Hoisting torque bias
input (valid only
when
=
)
%
1/0.01
-250- +250
100
0344 Lowering
torque
bias multiplier
%
1/0.01
0-100 100
0345 Brake
release
time
s
0.01/0.01
0.00-10.00 0.05
0346 Creeping
frequency
Hz
0.1/0.01
f240
-20.0
3.0
0347
Creeping time 2
s
0.01/0.01
0.00-10.00 0.10
0348
Braking time
learning function
- 1/1
0:Disabled
1: Learning (0 after adjustment)
0
0349
Acceleration/decele
ration suspend
function
- 1/1
0:Disabled
1:Parameter setting
2:Terminal input
0
6.19
0350
Acceleration
suspend frequency
Hz 0.1/0.01
0.0-
0.0
0351
Acceleration
suspend time
s 0.1/0.1
0.0-10.0
0.0
0352
Deceleration
suspend frequency
Hz 0.1/0.01
0.0-
0.0
0353
Deceleration
suspend time
s 0.1/0.1
0.0-10.0
0.0
0359 PID
control
waiting time
s 1/1
0-2400
0 6.20
0360
PID control
-
-
0: Disabled
1: Process type PID control
2: Speed type PID control
0
0361 Delay
filter
s 0.1/0.1
0.0-25.0
0.1
0362 Proportional
gain - 0.01/0.01
0.01-100.0
0.30
Содержание TOSVERT VF-MB1
Страница 350: ...2011 07 ...