E6581697
F-101
6
[Parameter setting]
Title
Function
Adjustment range
Default setting
f681
Analog output signal selection
0: Meter option (0 to 1mA)
1: Current (0 to 20mA) output
2: Voltage (0 to 10V) output
0
f684
Analog output filter
2-1000 (ms)
2
f691
Inclination characteristic of analog
output
0: Negative inclination (downward slope)
1: Positive inclination (upward slope)
1
f692
Analog output bias
-1.0 - +100.0 (%)
0.0
Note 1: With 0 to 20mAdc (4 to 20mAdc) output, or 0 to 10Vdc output, set
f681
to
1
or
2
.
■
Example of setting
f681
=1,
f691
=1,
f692
=0(%)
f681
=1,
f691
=1,
f692
=20(%)
0
20
(mA)
0
100%
Internal calculated value
4
20
(mA)
0
100%
f692
O
ut
pu
t c
u
rr
e
nt
Internal calculated value
f681
=1,
f691
=0,
f692
=100(%)
f681
=1,
691
=0,
f692
=100(%)
0
20
(mA)
0
100%
: Large gain
O
ut
pu
t c
u
rr
e
nt
Internal calculated value
4
20
(mA)
0
100%
: Small gain
f692
O
ut
pu
t c
u
rr
e
nt
Internal calculated value
,
The analog output inclination can be adjusted using the parameter
.