6
6.30 Tracing
functions
f740
: Trace selection
f741
: Trace cycle
f742
: Trace data 1
f743
: Trace data 2
f744
: Trace data 3
f745
: Trace data 4
Function
These parameters are used to memorize and read out the data collected at the time of tripping or triggering.
Up to 4 kinds of data can be selected from 43 kinds of data, and the data collected at 100 consecutive
points can be stored in memory as trace data.
Here is the time at which trace data is acquired.
Tripping: Data collected before the occurrence
Triggering: Data collected after triggering
Note: To read data on a PC.
Title
Function
Adjustment range
Default setting
f740
Trace
selection
0: Disabled
1: At tripping
2: At triggering
3: 1+2
1
f741
Trace cycle
0: 4ms
1: 20ms
2: 100ms
3: 1s
4: 10s
2
f742
Trace data 1
0-42
0
f743
Trace data 2
0-42
1
f744
Trace data 3
0-42
2
f745
Trace data 4
0-42
3
Note1: For saving trace data, do not disconnect power supply after inverter tripped.
Note2: When
f741
=
0
or
1
setting, set the value of
f678
(Constant at the time of filtering) lower than
f741
setting time (trace cycle time).