E6581697
F-15
6
[Parameter setting]
Title
Function
Adjustment range
Default setting
f107
Analog input terminal
selection (VIB)
0: 0-+10V
1: -10-+10V
0
0: Analog input for communications
VIB
-
analog input
1: VIA - analog input
VIB
-
contact input (Sink)
2: VIA - analog input
VIB
-
contact input (Source)
3: VIA
-
contact input (Sink)
VIB
-
contact input (Sink)
f109
Analog/logic input
selection (VIA/VIB)
4: VIA
-
contact input (Source)
VIB
-
contact input (Source)
0
f201
VIA input point 1 setting
0-100 (%)
0
f202
VIA input point 1 frequency
0.0-500.0 (Hz)
0.0
f203
VIA input point 2 setting
0-100 (%)
100
f204
VIA input point 2 frequency
0.0-500.0 (Hz)
*1
f209
Analog input filter
2-1000 (ms)
64
f210
VIB input point 1 setting
-100-+100 (%)
0
f211
VIB input point 1 frequency
0.0-500.0 (Hz)
0.0
f212
VIB input point 2 setting
-100-+100 (%)
100
f213
VIB input point 2 frequency
0.0-500.0 (Hz)
*1
f216
VIC input point 1 setting
0-100 (%)
0
f217
VIC input point 1 frequency
0.0-500.0 (Hz)
0
f218
VIC input point 2 setting
0-100 (%)
100
f219
VIC input point 2 frequency
0.0-500.0 (Hz)
*1
f810
Communication command
point selection
0: Disabled
1: Enabled
0
f811
Communication command
point 1 setting
0-100 (%)
0
f812
Communication command
point 1 frequency
0.0-
fh
(Hz)
0
f813
Communication command
point 2 setting
0-100 (%)
100
f814
Communication command
point 2 frequency
0.0-
fh
(Hz)
*1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Note 1: Do not set point 1 and 2 to the same value. If they are set to the same value,
err1
is displayed.