E6581697
K-13
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0363
Integral
gain -
0.01/0.01
0.01-100.0
0.20 6.20
0366 Differential
gain - 0.01/0.01
0.00-2.55
0.00
0367 Process
upper
limit
Hz 0.1/0.01
0.0-
*1
0368 Process
lower
limit
Hz 0.1/0.01
0.0-
0.0
0369 PID
control
feedback signal
selection
- -
0:
Disabled
1: VIA
2: VIB
3: VIC
4 to 6: -
0
0372 Process
increasing rate
(speed type PID
control)
s 0.1/0.1
0.1-600.0
10.0
0373 Process
decreasing rate
(speed type PID
control)
s 0.1/0.1
0.1-600.0
10.0
0375 Factory
specific
coefficient 3B
- -
-
- *
3
0376 Factory
specific
coefficient 3C
- -
-
-
0378
Number of pulse
train input
pps
1/1 100-5000
250 6.6.5
0380 PID
forward/reverse
characteristics
selection
- -
0:
Forward
1: Reverse
0
6.20
0382
Hit and stop
control
- -
0: Disabled
1: Enabled
2: -
0
6.18.2
0383
Hit and stop
control frequency
Hz 0.1/0.01
0.1-30.0 5.0
0384 Factory
specific
coefficient 3D
- -
-
- *
3
0385 Factory
specific
coefficient 3E
- -
-
-
0386 Factory
specific
coefficient 3F
- -
-
-
0389 PID
control
reference signal
selection
- -
0:
fmod
/
f207
selected
1: Terminal board VIA
2: Terminal board VIB
3:
fpid
4: RS485 communication
5: UP/DOWN from external logic
input
6: CANopen communication
7: Communication option
8: Terminal board VIC
9, 10: -
11: Pulse train input
0
6.20
0390 Factory
specific
coefficient 3G
- -
-
- *
3
0391 Hysteresis
for
lower-limit
frequency
operation
Hz 0.1/0.01
0.0-
ul
0.2
6.9.1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.