E6581697
F-22
6
Starting frequency
Output frequency (Hz)
0
Operation signal (F-CC)
Time
ON
OFF
6.7 Operation
frequency
6.7.1 Starting
frequency
f240
: Starting frequency
Function
The frequency set with
is put out as soon as operation is started.
Use the
parameter when a delay in response of starting torque according to the
acceleration/deceleration time is probably affecting operation. Setting the starting frequency to a
value from 0.5 to 3.0Hz is recommended. The occurrence of an overcurrent can be suppressed by
setting this frequency below the rated slippage of the motor.
[Parameter setting]
Title
Function
Adjustment range
Default setting
f240
Starting frequency
0.1-10.0 (Hz)
0.5