E6581697
K-24
11
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0778 Easy
setting
mode
parameter 28
- -
999
4.5
6.32
0779 Easy
setting
mode
parameter 29
- -
999
0780 Easy
setting
mode
parameter 30
- -
999
0781 Easy
setting
mode
parameter 31
- -
999
0782 Easy
setting
mode
parameter 32
- -
0-2999
(Set by communication number)
50
0799 Factory
specific
coefficient 7A
- -
-
- *3
*3: Factory specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.
Communication
parameters
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0800
Baud rate
-
-
3: 9600bps
4: 19200bps
5: 38400bps
4
0801
Parity
-
-
0: NON (No parity)
1: EVEN (Even parity)
2: ODD (Odd parity)
1
0802
Inverter number
-
1/1
0-247
0
0803
Communication
time-out time
s 0.1/0.1
0.0:
Disabled,
0.1-100.0
0.0
6.33.1
0804
Communication
time-out action
- -
0:
Alarm
only
1: Trip (Coast stop)
2: Trip (Deceleration stop)
0
0805
Communication
waiting time
s 0.01/0.01
0.00-2.00
0.00
0806
Setting of master
and slave for
communication
between inverters
-
-
0: Slave (0 Hz command issued in
case the master inverter fails)
1: Slave (Operation continued in case
the master inverter fails)
2: Slave (Emergency stop tripping in
case the master inverter fails)
3: Master (transmission of frequency
commands)
4: Master (transmission of output
frequency signals)
0
0808
Communication
time-out detection
condition
-
-
0: Valid at any time
1: Communication selection of
fmod
or
cmod
2: 1 + during operation
1