E6581697
G-16
7
7.3.3
Settings depending on voltage (-10 to +10 V) input
You can set the frequency settings by inputting an analog voltage signal of -10 to +10Vdc between the VIB and
CC terminals.
The following shows examples when the run command is input from the terminal.
Title
Function
Adjustment range
Default setting
Setting example
Command mode selection
0 – 4
1
(panel keypad)
0
(terminal board)
Frequency setting mode
selection
0 – 11
0
(setting dial 1)
2
(terminal board VIB)
Analog input terminal
selection (VIB)
0: 0-+10V
1: -10-+10V
0
1
(-10 - +10V)
Analog/logic input selection
(VIA/VIB)
0 – 4
0
0
(Analog input)
VIB input point 1 setting
0 - 100%
0
0
VIB input point 1 frequency
0.0 - 500.0Hz
0.0
0.0
VIB input point 2 setting
0 - 100%
100
100
VIB input point 2 frequency
0.0 - 500.0Hz
*1
50.0/60.0
Analog input filter
2 - 1000 ms
64
64
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Motor
IM
R/L1
U/T1
MCCB
Power
Supply
S/L2
T/L3
V/T2
W/T3
CC
FLC
VIB
PP
VF-MB1
Run and stop settings
You can switch between forward run (F)
and reverser run (R), and run/stop with
external signals.
Setting characteristics for the
frequency setting signal and operation
frequency
Set characteristics at two points in the
diagram below.
Connecting and calibrating the
frequency meter
Select the type of meter connected at
and calibrate.
Refer to section 3.4 for details.
Forward
run
Reverse
run
* Connect a single-phase
input model to R/L1 and
S/L2/N.
FLA
FLB
CC
F
R
S1
S2
S3
RES
±
0
-10 to +10 Vdc
%
Point 2
Point 1
Frequency setting signal
-100%
0%
100%
(-10V)
(0V)
(+10V)
Operation frequency (Hz)
Forward run
Reverse run