E6581697
K-14
11
Torque boost parameters 1
Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0: Auto-tuning disabled
1: Initialization of
(after
execution : 0)
2: Auto-tuning executed
(after execution: 0)
3: -
4: Motor constant auto calculation
(after execution: 0)
0400 Auto-tuning
-
-
5: 4+2 (after execution: 0)
0
6.21
0401 Slip
frequency
gain
% 1/1
0-150
50
0402 Automatic
torque
boost value
% 0.1/0.1
0.1-30.0
*
2
0405 Motor
rated
capacity
kW 0.01/0.01
0.01-22.00
*
2
0412 Motor
specific
coefficient 1
- -
-
-
*
4
0415 Motor
rated
current
A 0.1/0.1
0.1-100.0
*
2 6.21
0416 Motor
no-load
current
% 1/1
10-90
*
2
0417
Motor rated
speed
min-1
1/1 100-64000
*1
0441 Power
running
torque limit 1 level
% 1/0.01
0-249%,
250:Disabled
250 6.22.1
0443 Regenerative
braking torque
limit 1 level
% 1/0.01
0-249%,
250:Disabled
250
0444 Power
running
torque limit 2 level
% 1/0.01
0-249%,
250:Disabled
250
0445 Regenerative
braking torque
limit 2 level
% 1/0.01
0-249%,
250:Disabled
250
0451 Acceleration/decel
eration operation
after torque limit
- 1/1
0: In sync with acceleration /
deceleration
1: In sync with min. time
0
6.22.2
0452 Power
running
stall continuous
trip detection time
s
0.01/0.01
0.00-10.00
0.00 6.22.3
0454 Constant
output
zone torque limit
selection
- -
0:Constant output limit
1:Constant torque limit
0
6.22.1
0458 Motor
specific
coefficient 2
- -
-
-
*
4
0459 Load
inertia
moment ratio
Times
0.1/0.1 0.1-100.0
1.0
6.21
0460 Motor
specific
coefficient 3
- -
-
-
*
4
0461 Motor
specific
coefficient 4
- -
-
-
0462 Motor
specific
coefficient 5
- -
-
-
0467 Motor
specific
coefficient 6
- -
-
-
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*4: Motor specific coefficient parameters are manufacturer setting parameters. Do not change the value of these parameters.