Speed instruction (analog signal) settings from
external devices
Function of analog input terminals can be
selected from four functions (external
potentiometer, 0 to 10Vdc, 4 (0) to 20mAdc,
-10 to +10Vdc).
The selective function of analog input
terminals gives system design flexibility.
The maximum resolution is 1/1000.
Analog input terminal function settings
Terminal
symbol
Title
Function
Adjustment range
Default setting
-
Frequency priority selection
0, 1
0
VIA input point 1 setting
0 - 100%
0
VIA input point 1 frequency
0.0 - 500.0Hz
0.0
VIA input point 2 setting
0 - 100%
100
VIA
VIA input point 2 frequency
0.0 - 500.0Hz
*1
-
Frequency setting mode selection 2
0-11
1
VIA to VIC
Analog input filter
4 - 1000 ms Note 1)
64
VIB input point 1 setting
0 - 100%
0
VIB input point 1 frequency
0.0 - 500.0Hz
0.0
VIB input point 2 setting
0 - 100%
100
VIB
VIB input point 2 frequency
0.0 - 500.0Hz
*1
VIC input point 1 setting
0 - 100%
0
VIC input point 1 frequency
0.0 - 500.0Hz
0.0
VIC input point 2 setting
0 - 100%
100
VIC
VIC input point 2 frequency
0.0 - 500.0Hz
*1
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
Note1) When stable operation cannot be attained because of frequency setting circuit noise, increase
.
[Control terminal block]
FLA
FLC
FLB
CC
FM
CC
P24
CC
PP
VIB
VIC
VIA
RY
RC
OUT
NO
F
R
S1
S2
S3
RES
STO
+SU
SW2(S3)
LOGIC
PTC
SW1
SOURCE
PLC
SINK