Title
Communication
No.
Function Unit
Minimum
setting unit
Panel/Commun
ication
Adjustment range
Default
setting
User
setting
Reference
0009 Acceleration
time
1
s
0.1/0.1
0.0-3600 (360.0) *8
10.0
5.4
0010 Deceleration
time
1
s
0.1/0.1
0.0-3600 (360.0) *8
10.0
0011 Maximum
frequency
Hz 0.1/0.01
30.0-500.0
80.0
5.9
0012
Upper limit
frequency
Hz 0.1/0.01
0.5-
*1
5.10
0013
Lower limit
frequency
Hz 0.1/0.01
0.0-
0.0
0014
Base frequency 1
Hz
0.1/0.01
20.0-500.0
*1
5.11
0409 Base
frequency
voltage 1
V
1/0.1
50-330 (240V class)
50-660 (500V class)
*1 5.11
6.15.6
0015 V/F
control
mode
selection
-
-
0: V/F constant
1: Variable torque
2: Automatic torque boost control
3: Vector control
4: Energy-saving
5: Dynamic energy-saving
(For fan and pump)
6: PM motor control
7: V/F 5-point setting
8: -
*1 5.12
0016 Torque
boost
value 1
% 0.1/0.1
0.0-30.0
*2
5.13
0600 Motor
electronic-
thermal protection
level 1
%
(A)
1/1 10-100
100 3.5
5.14
6.24.1
Setting
Overload
protection
OL
stall
0 valid
invalid
1 valid
valid
2 invalid
invalid
3
Standard
motor
invalid valid
4 valid
invalid
5 valid
valid
6 invalid
invalid
0017 Electronic-thermal
protection
characteristic
selection
- -
7
VF motor
invalid valid
0 3.5
5.14
0018 Preset-speed
frequency 1
Hz 0.1/0.01
-
0.0
0019 Preset-speed
frequency 2
Hz 0.1/0.01
-
0.0
0020 Preset-speed
frequency 3
Hz 0.1/0.01
-
0.0
0021 Preset-speed
frequency 4
Hz 0.1/0.01
-
0.0
0022 Preset-speed
frequency 5
Hz 0.1/0.01
-
0.0
0023 Preset-speed
frequency 6
Hz 0.1/0.01
-
0.0
0024 Preset-speed
frequency 7
Hz 0.1/0.01
-
0.0
3.6
5.15
0025 Process
input
value of PID
control
Hz 0.1/0.01
f368
-
0.0 5.16
6.20
*1: Default setting values vary depending on the setup menu setting. Refer to section 11.5.
*2: Default setting values vary depending on the capacity. Refer to section 11.4.
*8: These parameters can be changed to 0.01s unit by setting
f519
=
1
.