E6581697
F-127
6
6.33.5 Open network option
c000
to
c119
: Communication option common parameters
c150
to
c199
: ProfiBus DP option parameters
c200
to
c249
: DeviceNet option parameters
c400
to
c449
: EtherCAT option parameters
c500
to
c549
: EtherNet common parameters
c550
to
c599
: EtherNet/IP option parameters
c600
to
c649
: Modbus TCP option parameters
c850
to
c899
: EtherCAT option parameters
c900
to
c909
: Communication option common parameters
+
ProfiBus DP option
(Type: PDP003Z)
DeviceNet option
(Type: DEV003Z)
EtherNet / IP-Modbus TCP option (Type: IPE002Z)
EtherCAT option
(Type: IPE003Z)
Refer to each Instruction Manual of option for details.
6.34 Permanent
magnet
motors
f910
: Step-out detection current level
f911
: Step-out detection time
f912
: q-axis inductance
f913
: d-axis inductance
Function
If the permanent magnet motor (PM motor) steps out and if the exciting current increases (it increases
in such a case) and remains above the value set with
f910
for the period of time set with
f911
,
the inverter will judge the motor to be stepping out and trip it. At that time, the trip message
"
sout
" is displayed.