Technical specifications
13.5 Technical specifications for I/O module
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
239
Article number
6BK1900-0CA00-0AA0
Measuring inputs for current
–
Current measurement range, min.
0 A
–
Current measurement range, max.
5 A
–
Relative measuring accuracy current
0.5 %
–
Operating frequency 1
50 Hz
–
Operating frequency 2
60 Hz
–
Design of electrical connection at the
measuring inputs for current
1x 8 pole connector with spring-loaded connec-
tion
–
Connectable conductor cross-sections,
solid
1x (0.2 ... 1.5 mm²)
–
Connectable conductor cross-sections,
finely stranded with wire end pro-
cessing
1x (0.25 ... 1.5 mm²)
–
Connectable conductor cross-sections
for AWG cables
1x (24 ... 16)
Isolation
Overvoltage category
III
Degree of pollution
2
EMC
EMC interference emission
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC 61000-4-
3
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
Conducted interference due to burst acc. to
IEC 61000-4-4
2 kV signal lines
Conducted interference due to surge acc. to
IEC 61000-4-5
Voltage measurement inputs: 1 kV balanced, 2
kV unbalanced
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection
IP20
Standards, approvals, certificates
Reference designation according to DIN EN
81346-2
K