Technical specifications
13.5 Technical specifications for I/O module
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
243
Article number
6BK1900-0AA00-0AA0
Potential separation
between the channels
No
Isolation
Overvoltage category
III
Degree of pollution
2
EMC
EMC interference emission
Limit value in accordance with IEC 61000-6-
4:2007 + A1:2011
Electrostatic discharge acc. to IEC 61000-4-2 4 kV contact discharge / 8 kV air discharge
Field-related interference acc. to IEC 61000-4-
3
10 V/m (80 ... 1 000 MHz), 3 V/m (1.4 ... 2.0
GHz), 1 V/m (2.0 ... 2.7 GHz)
Conducted interference due to burst acc. to
IEC 61000-4-4
2 kV signal lines
Conducted interference due to surge acc. to
IEC 61000-4-5
Not applicable
Conducted interference due to high-frequency
radiation acc. to IEC 61000-4-6
10 V (0.15 ... 80 MHz)
Degree and class of protection
IP degree of protection
IP20
Standards, approvals, certificates
Reference designation according to DIN EN
81346-2
K