Communications
10.3 Transfer of diagnostic alarms to the controller
SIPLUS HCS4200 PROFINET/PROFIBUS DP
178
Operating Instructions, 07/2019, A5E35066204A/006
PM error codes
Error code
(hex)
Description
PM Tem-
perature
PM DI/DO
PM U/I
0001
Short-circuit
–
✓
–
0006
Wire break
✓
✓
–
0007
Measurement range, high limit exceeded
✓
–
–
0008
Measurement range, low limit violated
✓
–
–
0011
No supply voltage
–
✓
–
5101
Communication error on HCS bus
✓
✓
✓
510C
Error is not defined.
✓
✓
–
5112
Polarity reversal at measuring input
✓
–
–
Note
The following applies for PM4000 DI/DO:
The error codes for short-circuit and wire breakage can each only be reported for a group of
4 channels. The number of the first channel of the group of 4 is entered as the channel
number.
Causes of error and remedies
You will find information about possible causes of error and remedies in Section Process and
system messages, error handling (Page 179).
Note
The following applies to channel faults 0x5104 to 0x5107 and 0x510C:
If a fault status changes on a channel, the first fault to be reported is retained.