Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
126
Operating Instructions, 07/2019, A5E35066204A/006
Station option with no POMs
Figure 8-4
Station option with no POMs
The associated control data record DS196 must be pre-assigned as follows:
Byte
Element
Code
Description
0
Block length
4 + 25
Header
1
Block ID
196
2
Version
1
3
Version
0
4
Slot 1 of station master
1
PM available
5
Slot 2 of station master
2
POM available
6
Slot 3 of station master
3
POM available
7
Slot 4 of station master
0
POM is not inserted in the station
options
8
Slot 5 of station master
0
POM is not inserted in the station
options
9
Slot 6 of station master
0
Module not available
…
…
28
Slot 25 of station master
0
Module not available
The data record can also be written in abbreviated form with length 4+5; the last entry is
byte 8 in this case.