Configuration
8.5 Configuration control (option handling)
SIPLUS HCS4200 PROFINET/PROFIBUS DP
120
Operating Instructions, 07/2019, A5E35066204A/006
Rules
Observe the following rules:
●
The feedback data record refers to the configured station configuration and always
includes the maximum configuration limits, which is 25 modules.
●
Partial reading of the feedback data record is not possible.
●
As long as a control data record is not sent, it is assumed that no modules are inserted
(DS197 has status "0").
Feedback data record
Table 8- 5
Feedback data record
Byte
Element
Code
Explanation
0
Block length
4 +
(number of slots x 2)
Header
1
Block ID
197
2
Version
2
3
0
4
Slot 1 status
0/1
Status = 1:
•
Module from station master is in-
serted in the station option
•
Slot is marked as not available in
the control data record
Status = 0:
•
Module pulled
•
Incorrect module inserted in the
station option*
5
Reserved
0
6
Slot 2 status
0/1
7
Reserved
0
:
:
:
53
Slot 25 status
0/1
54
Reserved
0
* Not possible if the slot is marked as not available.