Communications
10.3 Transfer of diagnostic alarms to the controller
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
177
Special features of POM 4220 Highend:
Connection type "2-pin switching"
Error code Meaning
Description
5104
Channels 1 to 4 Both Triacs are fused
The error message is generated
via channels 1 to 4.
Channels 5 to 8 Exactly one Triac has fused
The error message is generated
via channels 5 to 8.
5105
–
–
–
5107
Channels 1 to 4
•
External fault
•
Fuse F1 ... F8 is defective
•
Triac 1 … 8 has high re-
sistance
The error message is generated
via channels 1 to 4.
No distinction is possible between
an external fault and a fuse fault.
Therefore, the error code 5107
includes the following errors:
•
Channel fault "Triac has high
resistance" / "outgoing fuse
blown"
•
Channel fault "external fault".
See also section Fault reporting
(Page 180).
Channels 5 to 8 –
–
Connection type "economy circuit"
Error code Meaning
Description
5104
Channels 1 to 4 Triac 1 … 4 is fused
From the user’s point of view, only
channels 1 through 4 are used.
However, error messages 5104
and 5105 are generated specifical-
ly via channels 1 through 8.
Channels 5 to 8 Triac 5 … 8 is fused
5105
Channels 1 to 4
•
Fuse F1 ... F4 tripped
•
Triac 1 … 4 has high re-
sistance
Channels 5 to 8
•
Fuse F5 ... F8 tripped
•
Triac 5 … 8 has high re-
sistance
5107
Channels 1 to 4 External fault
–
Channels 5 to 8 External fault
–