Configuration
8.3 Device configuration and configuration parameters in the TIA Portal
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
111
Note
Normalizing the total power
•
When connecting the load between phase and N-conductor, the power ratings to be
configured must be normalized to 230 V.
•
When connecting the load between phase and phase, the power ratings to be configured
must be normalized to 400 V.
Calculation example for interconnection phase - N-conductor
Normalization:
P
scaled
= P
load
* (230 V/U
load
)
2
Load with U
rated
= 240 V; P
rated
= 1500 W
P
normalized
= 1500 W * (230 V/240 V)
2
P
normalized
= 1378 W
Calculation example for interconnection phase - phase
Normalization:
P
scaled
= P
load
* (400 V/U
load
)
2
Load with U
rated
= 480 V; P
rated
= 6000 W
P
normalized
= 6000 W * (400 V/480 V)
2
P
normalized
= 4167 W
Configuration parameters POM4320
Description
Value range
Control mode
(Set once per POM)
•
Half-wave control (default)
•
Soft start version 1
•
Soft start version 2
•
Soft start version 3
•
Phase angle control
1)
•
Phase angle control with Softstart version 1
•
Phase angle control with Softstart version 2
•
Phase angle control with Softstart version 3
)
Response to errors
(setting per channel)
•
Channel substitute value 0 (default)
•
Channel value is retained