Communications
10.1 Cyclic data exchange
SIPLUS HCS4200 PROFINET/PROFIBUS DP
Operating Instructions, 07/2019, A5E35066204A/006
159
10.1.2
Cyclic input data
Cyclic data exchange between the heating control system and the S7 takes place via the
process/I/O address area of the CPU. The cyclic data can be addressed in the S7 through
the process image or I/O commands.
Cyclic input data for CIM
Byte
Bit
Description
0
Status bits
0
Heater
0: Heating is switched off
1: Heating is switched on
1
Operating mode
0: Production mode
1: Standby mode
2
Line voltage compensation
0: is switched off
1: is switched on
3
0 (not in use)
4
0 (not in use)
5
0 (not in use)
6
0 (not in use)
7
0 (not in use)
1
–
0 (not in use)
Cyclic input data for POM4220 Low end
Byte
Description
0
Power output 1 actual value
1
Power output 2 actual value
2
Power output 3 actual value
3
Power output 4 actual value
4
Power output 5 actual value
5
Power output 6 actual value
6
Power output 7 actual value
7
Power output 8 actual value
8
Power output 9 actual value
9
Power output 10 actual value
10
Power output 11 actual value
11
Power output 12 actual value
12
Power output 13 actual value
13
Power output 14 actual value
14
Power output 15 actual value
15
Power output 16 actual value