103BCommunication
10.2 PROFINET
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
411
ERROR
STATUS
Description
1
80B4
TCON: When using the ISO on TCP (connection_type = B#16#12) to establish a
passive connection, condition code 80B4 alerts you that the TSAP entered did not
conform to one of the following address requirements:
For a local TSAP length of 2 and a TSAP ID value of either E0 or E1 (hexadecimal)
for the first byte, the second byte must be either 00 or 01.
For a local TSAP length of 3 or greater and a TSAP ID value of either E0 or E1
(hexadecimal) for the first byte, the second byte must be either 00 or 01 and all
other bytes must be valid ASCII characters.
For a local TSAP length of 3 or greater and the first byte of the TSAP ID does not
have a value of either E0 or E1 (hexadecimal), then all bytes of the TSAP ID must
be valid ASCII characters.
Valid ASCII characters are byte values from 20 to 7E (hexadecimal).
1
80B6
TCON: Parameter assignment error in parameter connection_type
1
80B7
TCON: Data type and/or length of the transmitted data does not fit in the area in the
partner CPU, in which it is to be written.
1)
80B8
TCON: Parameter in the local connection description and Parameter ID are different.
1
80C3
TCON: All connection resources are in use.
1
80C4
Temporary communications error:
The connection cannot be established at this time (TCON).
The configured connection is currently being removed by TDISCON (TCON).
The connection is currently being established (TDISCON).
The interface is receiving new parameters (TCON and TDISCON).