103BCommunication
10.3 PROFIBUS
S7-1200 Programmable controller
450
System Manual, 11/2011, A5E02486680-05
Thus, the addresses that may be used for PROFIBUS operational devices are 2 through
125.
In the Properties window, select the "PROFIBUS address" configuration entry. STEP 7
displays the PROFIBUS address configuration dialog, which is used to assign the
PROFIBUS address of the device.
Table 10- 38 Parameters for the PROFIBUS address
Parameter
Description
Subnet
Name of the Subnet to which the device is connected. Click the "Add new subnet" button to create a
new subnet. "Not connected" is the default. Two connection types are possible:
The "Not connected" default provides a local connection.
A subnet is required when your network has two or more devices.
Address
Assigned PROFIBUS address for the device
Highest address
The highest PROFIBUS address is based on the active stations on the
PROFIBUS (for example, DP master). Passive DP slaves independently
have PROFIBUS addresses from 1 to 125 even if the highest PROFIBUS
address is set to 15, for example. The highest PROFIBUS address is
relevant for token forwarding (forwarding of the send rights), and the token
is only forwarded to active stations. Specifying the highest PROFIBUS
address optimizes the bus.
Parameters
Transmission rate
Transmission rate of the configured PROFIBUS network: The PROFIBUS
transmission rates range from 9.6 Kbits/sec to 12 Mbits/sec. The
transmission rate setting depends on the properties of the PROFIBUS
nodes being used. The transmission rate should not be greater than the
rate supported by the slowest node.
The transmission rate is normally set for the master on the PROFIBUS
network, with all DP slaves automatically using that same transmission rate
(auto-baud).