553BTechnical specifications
A.1 General Technical Specifications
S7-1200 Programmable controller
660
System Manual, 11/2011, A5E02486680-05
Electromagnetic compatibility
Electromagnetic Compatibility (EMC) is the ability of an electrical device to operate as
intended in an electromagnetic environment and to operate without emitting levels of
electromagnetic interference (EMI) that may disturb other electrical devices in the vicinity.
Table A- 2
Immunity per EN 61000-6-2
Electromagnetic compatibility - Immunity per EN 61000-6-2
EN 61000-4-2
Electrostatic discharge
8 kV air discharge to all surfaces
6 kV contact discharge to exposed conductive surfaces
EN 61000-4-3
Radiated, radio-frequency,
electromagnetic field immunity test
80 to 1000 MHz, 10 V/m, 80% AM at 1 kHz
1.4 to 2.0 GHz, 3 V/m, 80% AM at 1 kHz
2.0 to 2.7 GHz, 1 V/m, 80% AM at 1 kHz
EN 61000-4-4
Fast transient bursts
2 kV, 5 kHz with coupling network to AC and DC system power
2 kV, 5 kHz with coupling clamp to I/O
EN 6100-4-5
Surge immunity
AC systems - 2 kV common mode, 1kV differential mode
DC systems - 2 kV common mode, 1kV differential mode
For DC systems (I/O signals, DC power systems) external protection is
required.
EN 61000-4-6
Conducted disturbances
150 kHz to 80 MHz, 10 V RMS, 80% AM at 1kHz
EN 61000-4-11
Voltage dips
AC systems
0% for 1 cycle, 40% for 12 cycles and 70% for 30 cycles at 60 Hz
Table A- 3
Conducted and radiated emissions per EN 61000-6-4
Electromagnetic compatibility - Conducted and radiated emissions per EN 61000-6-4
0.15 MHz to 0.5 MHz
<79dB (μV) quasi-peak; <66 dB (μV) average
0.5 MHz to 5 MHz
<73dB (μV) quasi-peak; <60 dB (μV) average
Conducted Emissions
EN 55011, Class A, Group 1
5 MHz to 30 MHz
<73dB (μV) quasi-peak; <60 dB (μV) average
30 MHz to 230 MHz
<40dB (μV/m) quasi-peak; measured at 10m
Radiated Emissions
EN 55011, Class A, Group 1
230 MHz to 1 GHz
<47dB (μV/m) quasi-peak; measured at 10m
Environmental conditions
Table A- 4
Transport and storage
Environmental conditions - Transport and storage
EN 60068-2-2, Test Bb, Dry heat and
EN 60068-2-1, Test Ab, Cold
-40° C to +70° C
EN 60068-2-30, Test Db, Damp heat
25° C to 55° C, 95% humidity
EN 60068-2-14, Test Na, temperature shock
-40° C to +70° C, dwell time 3 hours, 5 cycles
EN 60068-2-32, Free fall
0.3 m, 5 times, product packaging
Atmospheric pressure