System Manual, 11/2011, A5E02486680-05
12.5.2
Modbus TCP
12.5.2.1
MB_CLIENT (Modbus TCP)
Table 12- 49 MB_CLIENT instruction
LAD / FBD
SCL
Description
"MB_CLIENT_DB"(
REQ:=_bool_in_,
DISCONNECT:=_bool_in_,
CONNECT_ID=_uint_in_,
IP_OCTET_1:=_byte_in_,
IP_OCTET_2:=_byte_in_,
IP_OCTET_3:=_byte_in_,
IP_OCTET_4:=_byte_in_,
IP_PORT:=_uint_in_,
MB_MODE:=_usint_in_,
MB_DATA_ADDR:=_udint_in_,
MB_DATA_LEN:=_uint_in_,
DONE=>_bool_out_,
BUSY=>_bool_out_,
ERROR=>_bool_out_,
STATUS=>_word_out_,
MB_DATA_PTR:=_variant_inout_);
MB_CLIENT communicates as a
Modbus TCP client through the
PROFINET connector on the S7-
1200 CPU. No additional
communication hardware module
is required.
MB_CLIENT can make a client-
server connection, send a
Modbus function request, receive
a response, and control the
disconnection from a Modbus
TCP server.
Table 12- 50 Data types for the parameters
Parameter and type
Data type Description
REQ
In
Bool
FALSE = No Modbus communication request
TRUE = Request to communicate with a Modbus TCP server
DISCONNECT
IN
Bool
The DISCONNECT parameter allows your program to control connection
and disconnection with a Modbus server device.
If DISCONNECT = 0 and a connection does not exist, then MB_CLIENT
attempts to make a connection to the assigned IP address and port number.
If DISCONNECT = 1 and a connection exists, then a disconnect operation is
attempted. Whenever this input is enabled, no other operation will be
attempted.
CONNECT_ID
IN
UInt
The CONNECT_ID parameter must uniquely identify each connection within
the PLC. Each unique instance of the MB_CLIENT or MB_SERVER
instruction must contain a unique CONNECT_ID parameter.
IP_OCTET_1
IN
USInt
Modbus TCP server IP address: Octet 1
8-bit part of the 32-bit IPv4 IP address of the Modbus TCPserver to which
the client will connect and communicate using the Modbus TCP protocol.
IP_OCTET_2
IN
USInt
Modbus TCP server IP address: Octet 2
IP_OCTET_3
IN
USInt
Modbus TCP server IP address: Octet 3
IP_OCTET_4
IN
USInt
Modbus TCP server IP address: Octet 4
IP_PORT
IN
UInt
Default value = 502: The IP port number of the server to which the client will
attempt to connect and ultimately communicate using the TCP/IP protocol.