553BTechnical specifications
A.9 Analog signal boards (SBs)
S7-1200 Programmable controller
734
System Manual, 11/2011, A5E02486680-05
Table A- 134 Analog output representation for voltage
System
Voltage Output Range
Decimal
Hexadecimal
± 10 V
32767
7FFF
See note 1
32512
7F00
See note 1
Overflow
32511
7EFF
11.76 V
27649
6C01
Overshoot range
27648
6C00
10 V
20736
5100
7.5 V
1
1
361.7 μ V
0
0
0 V
-1
FFFF
-361.7 μ V
-20736
AF00
-7.5 V
-27648
9400
-10 V
Rated range
-27649
93FF
-32512
8100
-11.76 V
Undershoot range
-32513
80FF
See note 1
-32768
8000
See note 1
Underflow
1
In an overflow or underflow condition, analog outputs will behave according to the device configuration properties set for
the analog signal module. In the "Reaction to CPU STOP" parameter, select either: Use substitute value or Keep last
value.
A.9.4
Thermocouple SBs
A.9.4.1
SB 1231 1 analog thermocouple input specifications
Note
To use this SB, your CPU firmware must be V2.0 or higher.
Table A- 135 General specifications
Technical data
SB 1231 AI 1 x 16 bit Thermocouple
Order number
6ES7 231-5QA30-0XB0
Dimensions W x H x D (mm)
38 x 62 x 21 mm
Weight
35 grams
Power dissipation
0.5 W
Current consumption (SM Bus)
5 mA
Current consumption (24 VDC)
20 mA