103BCommunication
10.2 PROFINET
S7-1200 Programmable controller
406
System Manual, 11/2011, A5E02486680-05
Error and Status Parameters
Table 10- 6 TSEND_C and TRCV_C condition codes for ERROR and STATUS
ERROR
STATUS
Description
0
0000
Job executed without error
0
7000
No job processing active
0
7001
Start job processing, establishing connection, waiting for connection partner
0
7002
Data being sent or received
0
7003
Connection being terminated
0
7004
Connection established and monitored, no job processing active
1
8085
LEN parameter is greater than the largest permitted value.
1
8086
The CONNECT parameter is outside the permitted range.
1
8087
Maximum number of connections reached; no additional connection possible.
1
8088
LEN parameter is not valid for the memory area specified in DATA.
1
8089
The CONNECT parameter does not point to a data block.
1
8091
Maximum nesting depth exceeded.
1
809A
The CONNECT parameter points to a field that does not match the length of the
connection description.
1
809B
The local_device_id in the connection description does not match the CPU.
1
80A1
Communications error:
The specified connection was not yet established
The specified connection is currently being terminated; transmission over this
connection is not possible
The interface is being reinitialized
1
80A3
Attempt being made to terminate a nonexistent connection
1
80A4
IP address of the remote partner connection is invalid. For example, the remote partner
IP address is the same as the local partner IP address.
1
80A5
Connection ID is already in use.
1
80A7
Communications error: You called TDISCON before TSEND_C was complete.
1
80B2
The CONNECT parameter points to a data block that was generated with the keyword
UNLINKED.
1
80B3
Inconsistent parameters:
Error in the connection description
Local port (parameter local_tsap_id) is already present in another connection
description.
ID in the connection description different from the ID specified as parameter