103BCommunication
10.5 S7 communication
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
467
Connection ID parameter
There are three ways to change the system-defined connection IDs:
1.
The user can change the current ID directly on the GET/PUT block. If the new ID belongs
to an already existing connection, the connection is changed.
2.
The user can change the current ID directly on the GET/PUT block, but the new ID does
not already exist. A new S7 connection is created by the system.
3.
The user can change the current ID through the "Connection overview" dialog: The user-
input is synchronized with the ID-parameter on the corresponding GET/PUT block.
Note
The parameter "ID" of the GET/PUT block is not a connection name, but a numerical
expression which is written like the following example: W#16#1
Connection name parameter
The connection name is editable through a special user control, the "Connection overview"
dialog. This dialog offers all the available S7 connections which could be selected as an
alternative for the current GET/PUT communication. The user can create a completely new
connection in this table. Click the button to the right of the "Connection name" field to start
the "Connection overview" dialog.