553BTechnical specifications
A.7 Thermocouple and RTD signal modules (SMs)
S7-1200 Programmable controller
System Manual, 11/2011, A5E02486680-05
709
Table A- 92 Analog output representation for voltage
System
Voltage Output Range
Decimal
Hexadecimal
± 10 V
32767
7FFF
See note 1
32512
7F00
See note 1
Overflow
32511
7EFF
11.76 V
27649
6C01
Overshoot range
27648
6C00
10 V
20736
5100
7.5 V
1
1
361.7 μ V
0
0
0 V
-1
FFFF
-361.7 μ V
-20736
AF00
-7.5 V
-27648
9400
-10 V
Rated range
-27649
93FF
-32512
8100
-11.76 V
Undershoot range
-32513
80FF
See note 1
-32768
8000
See note 1
Underflow
1
In an overflow or underflow condition, analog outputs will behave according to the device configuration properties set for
the analog signal module. In the "Reaction to CPU STOP" parameter, select either: Use substitute value or Keep last
value.
A.7
Thermocouple and RTD signal modules (SMs)
A.7.1
SM 1231 Thermocouple
Table A- 93 General specifications
Model
SM 1231 AI 4 x 16 bit TC
SM 1231 AI 8 x 16 bit TC
Order number
6ES7 231-5QD30-0XB0
6ES7 231-5QF30-0XB0
Dimensions W x H x D (mm)
45 x 100 x 75
45 x 100 x 75
Weight
180 grams
190 grams
Power dissipation
1.5 W
1.5 W
Current consumption (SM Bus)
80 mA
80 mA
Current consumption (24 VDC)
1
40 mA
40 mA
1
20.4 to 28.8 VDC (Class 2, Limited Power, or sensor power from PLC)