9.3 Basic motion control
S7-1200 Programmable controller
364
System Manual, 11/2011, A5E02486680-05
Command type
Description
Velocity setpoint
Moves the axis at the given velocity.
Wait
Waits until the given period is over. "Wait" does not stop an active traversing motion.
Separator
Adds a "Separator" line above the selected line. The separator line acts as a range limit
for the graphic display of the trend view.
Prerequisites for MC_CommandTable execution:
●
The technology object TO_Axis_PTO V2.0 must be correctly configured.
●
The technology object TO_CommandTable_PTO must be correctly configured.
●
The axis must be released.
Override response
The MC_CommandTable task can be
aborted by the following motion control
tasks:
MC_Home Mode = 3
MC_Halt
MC_MoveAbsolute
MC_MoveRelative
MC_MoveVelocity
MC_MoveJog
The new MC_CommandTable task aborts the
following active motion control tasks:
MC_Home Mode = 3
MC_Halt
MC_MoveAbsolute
MC_MoveRelative
MC_MoveVelocity
MC_MoveJog
MC_CommandTable
The current motion control job with the
launch of the first "Positioning Relative",
"Positioning Absolute", "Velocity setpoint"
or "Halt" command