103BCommunication
10.5 S7 communication
S7-1200 Programmable controller
466
System Manual, 11/2011, A5E02486680-05
Table 10- 47 Connection parameter: General definitions
Parameter
Definition
End point
"Local End point": Name assigned to the Local CPU
"Partner End point": Name assigned to the Partner (remote) CPU
Note: In the "Partner End point" dropdown list, the system displays all potential
S7 connection partners of the current project as well as the option
"unspecified". An unspecified partner represents a communication partner
which is not currently in the STEP 7 project (for example, a third party device
communication partner).
Interface
Name assigned to the interfaces
Note: The user can change the connection by changing the Local and Partner
interfaces
Interface type
Type of interface
Subnet name
Name assigned to the subnets
Address
Assigned IP addresses
Note: The user can specify the remote address of a third party device for an
"unspecified" communication partner.
Connection ID
ID number: Automatically generated by the GET/PUT connection parameter
assignment
Connection name
Local and Partner CPU data storage location: Automatically generated by the
GET/PUT connection parameter assignment
Active connection
establishment
Checkbox to select Local CPU as the active connection
Connection
parameter:
General
One-way
Checkbox to specify a one-way or two-way connection; read-only
Note: In a PROFINET GET/PUT connection, both the local and partner
devices can act as a server or a client. This allows a two-way connection, and
the "One-way" checkbox is unchecked.
In a PROFIBUS GET/PUT connection, in some cases, the Partner device can
only act as a server (for example, an S7-300), and the "One-way" checkbox is
checked.